by zamalek
498 days ago
|
|
> Any imbalance I watched de-Bauer's analysis this morning, and you've seemingly hit the nail on the head. Even on his test bench it looks like only two of the wires are carrying all of the power (instead of all of them, I think 4 would be nominal?) - using a thermal camera as a measuring tool. The melted specimen also has a melted wire. Maybe 24V or 48V should be considered, and higher gauge wires - yes. |
|
As others no doubt mention Power (loss, Watts) = I (amsp) * V (volts (delta~change on the wire)).
dV = I*R ==> dV = I * I / R -- That is, other things being equal, amps squared is the dominant factor in how much power loss occurs over a cable. In the low voltage realms most insulators are effectively the same and there's very little change in resistance relative to the voltages involved, so it's close enough to ignore.
600W @ 12V? 50A ==> 1200 * R while at 48V ~12.5A ==> 156.25 * R
A 48V system would have only ~13% the resistive losses over the cables (more importantly, at the connections!); though offhand I've heard DC to DC converters are more efficient in the range of a 1/10th step-down. I'm unsure if ~1/25th would incur more losses there, nor how well common PC PCB processes handle 48V layers.
https://en.wikipedia.org/wiki/Low_voltage#United_States
""" In electrical power distribution, the US National Electrical Code (NEC), NFPA 70, article 725 (2005), defines low distribution system voltage (LDSV) as up to 49 V.
The NFPA standard 79 article 6.4.1.1[4] defines distribution protected extra-low voltage (PELV) as nominal voltage of 30 Vrms or 60 V DC ripple-free for dry locations, and 6 Vrms or 15 V DC in all other cases.
Standard NFPA 70E, Article 130, 2021 Edition,[5] omits energized electrical conductors and circuit parts operating at less than 50 V from its safety requirements of work involving electrical hazards when an electrically safe work condition cannot be established.
UL standard 508A, article 43 (table 43.1) defines 0 to 20 V peak / 5 A or 20.1 to 42.4 V peak / 100 VA as low-voltage limited energy (LVLE) circuits. """
The UK is similar, and the English Wikipedia article doesn't cite any other country's codes, though the International standard generally talks at the power grid distribution level.