|
|
|
|
|
by zaarn
2408 days ago
|
|
Atleast in germany the standard breakers don't either but the GFCI does and 3-phase breakers need to interrupt all phases. The neutral is also somewhat regularly grounded in the building's I've seen and atleast one grounding point is required at the distro point. Plus the breakers will trip at 50A inrush anyway. (From experience, 50V AC won't kill you unless you are standing in a bathtub and covered yourself in conductive gel, you'll just get some minor pain in most cases) |
|
Hmm. Are phase-to-neutral loads permitted? If so, does this mean that the building and ground are allowed to carry neutral currents? This seems like a bad idea.
I’m not an electrician, but I’ve seen enough problems caused by “objectionable current” (the US code name for currents through what is supposed to be ground even in the absence of a fault) that I think that neutral should be treated as a hot wire whose voltage to ground just happens to be quite low. This would involve all breakers switching the neutral as well as having a reliable mechanism to detect neutral-to-ground faults.
Newer US GFCI devices are supposed to detect neutral-to-ground faults, so that’s a start, but I don’t think any of them will actually disconnect the neutral if such a fault is detected. They do this by inductively coupling a low voltage 120 Hz common mode waveform on hot + neutral, or maybe just on neutral. It’s a cute trick.