by amluto
2408 days ago
|
|
> The neutral is also somewhat regularly grounded in the building's I've seen and atleast one grounding point is required at the distro point. Hmm. Are phase-to-neutral loads permitted? If so, does this mean that the building and ground are allowed to carry neutral currents? This seems like a bad idea. I’m not an electrician, but I’ve seen enough problems caused by “objectionable current” (the US code name for currents through what is supposed to be ground even in the absence of a fault) that I think that neutral should be treated as a hot wire whose voltage to ground just happens to be quite low. This would involve all breakers switching the neutral as well as having a reliable mechanism to detect neutral-to-ground faults. Newer US GFCI devices are supposed to detect neutral-to-ground faults, so that’s a start, but I don’t think any of them will actually disconnect the neutral if such a fault is detected. They do this by inductively coupling a low voltage 120 Hz common mode waveform on hot + neutral, or maybe just on neutral. It’s a cute trick. |
|
We use the TN-C-S system, wherein before the GFCI you have 3-phase with a PEN that is shorted to ground when it enters the building, then it is split into PE and N wires. The GFCI is 3-phase with only 1 phase being put into the building (usually, though multiple phases aren't uncommon in larger housings). The PE wire is connected to the heating system and various other ground potential points (either to provide ground or obtain ground potential). The N wire is shorted to PE before entering the socket (or the socket itself shorts these two). Once it leaves a socket the entire thing becomes unpolarized, so to speak, so devices after the socket can't short PE and N without polarized plugs.
This avoids problems with the inrush since the inrush voltage against ground will be grounded away shortly after entering the socket (and trip your breakers). It also means that it's less likely that a single broken wire results in the entire GFCI becoming useless, though if neutral is broken it can become somewhat dangerous (but the device stops working).