by ars
2514 days ago
|
|
The reason for having ground is simply because if an electrician makes a mistake and reverses the hot and neutral, and you plug something in, the body of the device will now be connected to hot, and you'll get a shock. By having a separate ground, it's harder to mess that up, and devices can connect the body of the device to that. Inside the electrical box (mains) the neutral and ground are connected together, and are at the same potential. The only reason they run separate wires is in case of of mistakes. |
|
Erm no.
1. In case the neutral gets disconnected, so the frame isn't at the potential of the hot (no voltage drop across the device)
2. So the return voltage drop in the white wire isn't on the body of the device. ~20 volts between adjacent high-current appliances on different phases probably wouldn't be terribly dangerous to most people, but it is sloppy.
3. For GFCI/RCD, it separates bona fide return currents from "accidental" return currents. With only two wires, dropping a toaster into a (PVC-drain) bathtub wouldn't trip. (Erm, I just realized most toasters are actually only two wires. Well uh, don't do that).