by angry_octet
5 hours ago
|
|
There are multiple circuits on each phase, you would still need to limit current per outlet to 10A (8A sustained). If it's a dedicated circuit then 15A is fine, but usually that means a separate run, and in that case you can just have 20A or 32A. When you have "three phase 415v", the 415v is the phase-to-phase voltage. Unlike the US 180 degree split phase 220v or 208v p2p, consumer equipment is not wired phase-to-phase unless it is 3-phase. It's interesting that Europe has 3 phase cooktops, we usually see 32A single phase in Australia, homes rarely need more than 7kW per circuit. Aircons, pool heat pumps and EV chargers are the 3p loads. Getting a 3 phase PV inverter is worthwhile if you have sun synchronous loads, like pool heater/chillers, across the phases. Then you will want a 3p battery inverter for the same reasons. |
|