> The power people talk about arc flash protection and worker safety.

800VDC is insanely scary stuff.

> At present, no consensus standard provides a validated methodology for calculating direct current (dc) arc-flash incident energy.

This means that establishing proper PPE for DC arc flashes is not possible right now. If I was asked to provide electricians to work on these racks, I would only allow my electricians to approach them, let alone do any work, if they were de-energized, full stop. Even inspecting anything while they’re energized (without doing any work) would be insane, in my opinion. Nobody’s life is worth losing over a rack of servers, and the incident energy for a 480V AC circuit that can power a 1 MW rack (1503 amps) can exceed 40 cal per cm^2 depending on the electrical system already, and there is no PPE that protects you above that incident energy level.

2 comments

Subway and trolley traction power is at those levels. SF Muni overhead is 600VDC. BART is 1000VDC. Caltrain is 25,000VAC, because it was wired for high speed rail.
800VDC at (merely) hundreds of amps is a high-end electric car charger. (Those are a lot easier to shut down individually, though.)