Yeah, I wasn't planning to run the cold loops through the existing radiator piping. I just want the ability to cool at least 1 room by reusing the air-to-water system, even if that means the FPU requires its own piping from the outside. In that scenario, are FPUs a good option? Are there other drawbacks? |
|
Insulate all piping properly, the outdoor part will freeze in winter, and the indoor part will drip in summer if you don't. The best products for this are foamed rubber based. Make the insulation seamless with the right glue or tape, every opening will drip.
Add manual or automatic valves to shut off the heating loops in summer, so you don't accidentally get cold water in there. Your cold water loop might also need an extra circulation pump, depending on how you run your piping, but that's hard to say without a lot more detail.
FCUs are available in the same form factors as indoor units for refrigerant-based systems, including a thermostat remote control, e.g. https://www.sinclair-solutions.com/files/user-manual-en/fan-... . But get one from the manufacturer of your outdoor unit, so the communication lines work, e.g. so the indoor unit can instruct the outdoor unit to start/stop/regulate.