The GPU alone has a TDP of 700W, together with everything else (CPU, RAM, storage, fans) you're looking at 1500W+. Depending on the country, that may be enough to saturate your home's electricity uplink...
In North America we are on 120V, making a standard 15A outlet only 1500W max, and something like 1200W sustained. To use higher wattage appliances, we have to upgrade our outlets to 20A (2000/1600W) or up our voltage to 240V, but that carries a different set of plugs and outlets as well.
Usually the home service is 200+ amps these days which is 24 KW total across all circuits, though you're right that most individual circuits are only 10-15 amp.
1,800 watt for periods less then 3 hours and 1,440 watts for continuous loads over 3 hours.
Realistically, a 15A breaker won’t trip on a 2,300 watt load for at least a few minutes, and often not until a few hours. A listed breaker is expected to trip in several seconds to 3 minutes for a 3,600 watt continuous load.
Take all those numbers and go up by 33% for a house or apartment with 20A circuits (quite common). Go up by 667% for an oven plug.
As anyone who takes care of rentals during winter knows, a typical circuit can tolerate two 1,500 W space heaters without tripping very much (although this is unsafe and a bad idea).
Sorry, I was doing conservative napkin math, better safe than burnt to a crisp, as grandpa NEVER said... I'm currently having to rewire a lot of the house that he built and I bought so he could retire. There have been a lot of electrical issues that the inspection never found.
He hated outlets, and hardwired almost every appliance directly into whatever circuit was closest that fit the amperage, including literally cutting the plug off a cord, to nut the wires directly into the Romex.
I still haven't found what circuit my range hood is on. I turned off all 120V and it remained blowing, and knowing grandpa, he powered it off a single leg of a 240V. And I know he didn't use junction boxes, so the splices are likely all inside the walls.
In the US they have a 120V system so it might actually saturate a normal socket over there. My PC room has a 16A fuse and 230V though, so should be plenty :)
The US has a 240V system for residential power, not a 120V system.
Most homes in the US have 200 amp service. That's 48 kW of power available to the house, though code states that you can only pull 80% of that continuously, so 160 amp/38.4 kW.
The 120V misconception comes from the fact that it is delivered as split phase on two 120V legs. Any competent electrician can run a 240V, 50-amp (40 amps/9.6 kW continuous) circuit to any room in a house. Plenty of homes have these circuits for electric ranges, EV chargers, or RV power outlets, and there's nothing stopping anyone from having one of these circuits installed in whatever room they'd like it installed in.
Heck, my old landlord and I installed one ourselves to provide an outlet for an EV charger in the garage of a house I lived in about a decade ago.
400 amp and even higher service is available, though it is fairly uncommon. Plenty of large houses will have a 400-amp service, though, which means you can double the power numbers available that I mentioned above.
gotcha. I've never heard of 16amp service, in Canada we have 15 amp.
But its very common to have many 15amp and 240V lines run in a house in Canada.
My kitchen alone has 4 different lines. i don't think your scenario is all that uncommon given that almost all new builds will have the same lines run in their home.
That's actually less bad than I assumed. High-end gaming GPUs are already almost at 600W with peak usage above that. I assumed it was much worse than that; that seems absolutely feasible for running at home.
> […] you're looking at 1500W+. Depending on the country, that may be enough to saturate your home's electricity uplink...
1500W is the power of the typical American microwave or (tea) kettle at 120V. (Convert over to a NEMA 6 plug and dual-pole breaker and you can get 3000W.)
3000W is nothing special in the rest of the world with >200V wall plugs.
Never heard electrical uplink before but to those wondering Italy, India, and Japan all have requirements around 3kw. I was slightly surprised by this, but in the end if your running this in a tiny space with that low of power your already probably not buying used H100s.