by throwaway173738
114 days ago
|
|
> Similarly the 240v version of this plug (6-15/6-20) has the same property: 15amp and 20amp versions. The 15 amp is two horizontal blades. The 20 amp is one horizontal + 1 vertical but swapped places compared to the 120v version. I do wish more builders installed the 240v receptacles in kitchens in the US. There is no technical reason we can't have higher power kettles and whatnot. If code required these in garages and kitchens more appliances would be available for them. If we had more 240v circuits in garages and on the outside of the house you could use electric motors for more yard tasks. Batteries and gasoline is used often in the US because our branch circuits provide about half the power of a 240v branch circuit. You can buy electric mulchers that are powerful enough to grind tree limbs but they can’t run on a 120v circuits. |
|
We get 3 phases to each home, phase to neutral is 127v, and that's the standard voltage, so loads are divided over the 3 phases.
230v we get through phase to phase connections. We also balance those for the 220v loads, but it's kinda risky due to the nature of our grid, being an island.
Whenever there's a fault they disconnect the zone affected but sometimes in the process we get VERY short but massive overvoltage events.
Since everybody generally uses 127v, as the system trips the 127v line voltage increases for a bit, often within spec but because we take 230v from between the phases it spikes to heights beyond spec and burns the devices.