|
|
|
|
|
by foobarian
196 days ago
|
|
The atmosphere is in the way even at night, and re-radiates the energy. The effective background temperature is the temperature of the air, not to mention it would only work at night. I think there would need to be like 50-ish acres of radiators for a 50MW datacenter to radiate from 60 to 30C. This would be a lot smaller in space due to bigger temp delta. Either way opex would be much much less than average Earth DC (PUE almost 1 instead of run-of-the mill 1.5 or as low as 1.1 for hyperscalers). But yeah the upfront cost would be immense. |
|