by xenadu02
235 days ago
|
|
This is best practice for anyone who uses three phase power. A machine shop should connect 1/3 of their lights to each phase so it is immediately obvious if a phase gets dropped. Lots of equipment will suffer on two of three phases but with lower performance or even damage. |
|
No, it’s not. It’s a neat trick that visually reveals when the utility drops a phase, but there are better ways to handle avoiding equipment damage.
Best practice is to use phase monitoring relays that can de-energize a motor when a phase is dropped/reversed to prevent damage. The trip time is adjustable and it’s more reliable than manually hitting an e-stop. It also won’t let a motor with incorrect phasing start up either. You see phase loss relays on a lot of compressor motors and other large motors.
Here’s a flyer for an Eaton product: https://www.eaton.com/content/dam/eaton/products/industrialc...