The study is about VOCs. You’ll want a carbon filter, as even a HEPA filter won’t do much. Also, don’t put a HEPA filler in your HVAC return — not only is it unhelpful overkill, it will have excessive static pressure drop, thus wasting power, increasing noise, reducing airflow, and potentially damaging the blower. Use an appropriate filter in the MERV 13-16 range. |
|
If you're considering one, make sure to get an air purifies where the carbon filter can be changed independently from the main filter.