This doesn't make sense. Wall plugs (like circuit breakers) are designed for a particular max amperage draw. If I have a 10A 120V circuit and wall plug, I can't charge my car at 8A? I have wall ovens that connect via a 50A circuit. Do I need to worry about fire hazards when I bake something for hours and hours? |
|
It's complicated. Heat builds up over time. So for example your standard 15 amp breaker on a 14 gauge wire in the US is rated for 15 amps of intermittent use, but if you draw that continuously without letting the heat dissipate it becomes a fire hazard. IIRC circuits are generally rated for ~80% of their max load for continuous use, so that 15 amp circuit is considered good for 12 continuous. Or in your 10 amp example 8 should be ok.
Your oven and circuit should be sized such that your long cooks aren't a concern, if you look at it's label you'll probably find it has a max draw of well below 50amps, but if you have actual doubts ask a professional.