by jchw
312 days ago
|
|
The voltage is always going to be the same because the voltage is determined by the transformers leading to your service panel. The breakers break when you hit a certain amperage for a certain amount of time, so by installing a bigger breaker, you allow more amperage. If you actually had an electrician do it, I doubt they would've installed a breaker if they thought the wiring wasn't sufficient. Truth is that you can indeed get away with a 20A circuit on 14 AWG wire if the run is short enough, though 12 AWG is recommended. The reason for this is voltage drop; the thinner gauge wire has more resistance, which causes more heat and voltage drop across the wire over the length of it, which can cause a fire if it gets sufficiently hot. I'm not sure how much risk you would put yourself in if you were out-of-spec a bit, but I wouldn't chance it personally. |
|