The refrigerant is closed loop, but the condensers are sprayed with water which are much more efficient at removing heat than a fan + air. I did some research on additional cost of water + increased efficiency of the condenser, but it's not just that. The water needs to be treated, otherwise it leaves way too much sediment. |
|
By the way "spray the condenser" technology is very very rare because it's pretty much worst of both worlds and nowhere near as good or efficient as a cooling tower but much more maintenance than a dry cooler + compressor. Typically for high efficiency modern sites you'd be looking at cooling towers or dry cooler + compressor for water facilities or spray the water directly onto the air (direct or indirect adiabatic) for air based facilities.
To complicate things many (typically city DCs/Colos/ enterprise facilities) are air based facilities that convert to water by using heat exchangers in the datahalls.