Report on a smaller event in the UK: https://www.ofgem.gov.uk/publications/investigation-9-august... (see linked pdf) That started from a combination of a lightning strike and generator trip, but turned into a local cascade failure as lots of distributed generation noticed that the frequency was under 49Hz and disconnected itself. I suspect the Spanish situation will be similar - inability to properly contain a frequency excursion, resulting in widespread generator trips. (I suspect this is going to restart a whole bunch of acrimony about existing pain points like grid maintenance, renewables, domestic solar, and so on, probably with the usual suspects popping up to blame renewables) |
Renewables were a factor in the blackout here in Brazil a couple of years ago: the models used by the system operator did not correspond to reality, many solar and wind power plants disconnected on grid disturbances quicker than specified. That mismatch led the system operator to allow a grid configuration where a single fault could lead to a cascade (more power was allowed through a power line than could be redistributed safely if that power line shut off for any reason), and that single fault happened when a protection mechanism misbehaved and disconnected that power line. The main fix was to model these solar and wind power plants more conservatively (pending a more detailed review of their real-life behavior and the corresponding update of the models), which allowed them to correctly limit the power going through these power lines.
If you want an excruciating level of detail, the final 614-page report is at https://www.ons.org.br/AcervoDigitalDocumentosEPublicacoes/R... (in Portuguese; the main page for that incident is at https://www.ons.org.br/Paginas/Noticias/Ocorr%c3%aancia-no-S...).