by bewaretheirs
592 days ago
|
|
Something similar was at work in the 2018 natural gas explosions in and around Andover, MA:
https://en.wikipedia.org/wiki/Merrimack_Valley_gas_explosion... "According to the NTSB's preliminary report, customers in the accident area received gas from a low-pressure (0.5 psi) distribution network which, in turn, was fed from a high-pressure (75 psi) main pipeline via regulators controlled by sensors measuring pressure in the low-pressure pipes. At the time of the accident, workers were replacing some of the low-pressure piping, but the procedure set out by Columbia Gas for doing this failed to include transfer of a regulator's pressure sensor from the old, disused piping to the new. As a result, when the old pipe was depressurized, the regulator sensed zero pressure on the low-pressure side and opened completely, feeding the main pipeline's full pressure into the local distribution network." |
|