by quickthrowman
704 days ago
|
|
> The utility is in charge of taking the power from the grid and delivering 110/220V to end customers, i.e. homes and businesses. Sorry to be pedantic, but most US businesses have 208/120V or 480/277V three-phase electrical services. There are some old existing 240/120V three-phase high-leg delta (aka bastard leg) delta services. [0] Delta-wye transformers are the most common type today, that’s where you get the 208/120 and 480/277 services from. [1] Larger commercial/industrial customers can have their own medium/high voltage substations and premises wiring/distribution. Medium voltage is 2.4kV to 70kV with 4160V and 13800V being the most common for commercial/industrial applications. High voltage is roughly 100kV to 1mV. [0] https://en.m.wikipedia.org/wiki/High-leg_delta [1] https://en.m.wikipedia.org/wiki/Delta-wye_transformer |
|
Sorry to be pedantic, but define “business”. As someone who’s worked on many job sites doing commercial electrical work, it’s not as common as you imply that there’s three phase service running to a business. Do a lot have it, yes, most, no. Literally everything else you said I’m aligned with.