751 days ago
|
|
Is there still a N needed for 3phase? The big selling point of triphased power is that you don't need a neutral line, which is obviously a big benefit for transport. Is there a benefit to add a neutral line for battery loading? |
|
No on the distribution network (aka up to the transformer in the street usually, but for sure not on the xxx kV lines) because there the lines are balanced.
In your house, you do, because the voltage between 2 phases is 400V, but the voltage between 1 phase and N is 230V. So you have "low" voltage for "normal" appliances, but high-voltage (and thus high-power) available for high power applications. For example: EV charging, induction cooking, home heating / AC etc.
For an EV usually the N wouldn't be needed, if you always charged at a balanced power on all phases. But from my experience, the full 3 phase power is only used when the battery is empty. At some point the charger switches back to single phase to better modulate the current I guess.
Sidenote:
On a 3x230V net, you don't have an N, but that means you also don't have a non-power conducting wire either! Meaning: double pole switches and breakers are required to prevent shocks. This is why these are generally required in Belgium btw.
See also Y vs Δ distrubution nets: https://www.allaboutcircuits.com/textbook/alternating-curren...