from the looks of it, his CTs are mis-reporting/double counting. A very common problem with tesla installs. My solar roof had the same issue initially, and electricians really thought it was generating more then the rating of the inverters, until I fixed it (software controlled). With 3 inverters he can't have more than ~23kw AC (assuming each is 7.8kw, which is the largest inverters tesla had at the time). My solar roof is a bit smaller (~21kw), in a similar region, but the daily peaks are slightly less than half of what he was showing. |
|
What was the software fix? Was there some config that wasn't set correctly?