I've had a bunch of APC SmartUPS 1500 in both tower and rack formats. I found the batteries in the rack version, where batteries lay on their sides, reach end of life much sooner than the tower version, where batteries are upright. It's likely poorer heat dissipation/ventilation in the rack version, but may have to do with battery orientation. The rack version also seems to suffer corrosion damage from battery off-gasing if batteries reach critical failure and overheat. I haven't seen the same damage on the tower units. Again some combination of orientation and ventilation. |
|
Typically, what determines the life of these batteries is # of cycles and # of deep discharges. The more extreme the environment the shorter the life time. I have network equipment sit outdoors in a cabinet. The batteries typically last 24-36 months instead of the 48-60 months I see from indoor UPSes.