by sokoloff
1258 days ago
|
|
It can make leaving water temps (LWT) of 70°C. It can work when it's as cold as -28°C outside. What it can't do is both at the same time: make 70°C LWT when it's -28°C outside. It's designed for 65°C LWT (some models 60°C) and can only reach 70°C at a performance penalty (year-round) and can only maintain 70°C LWT down to -15°C and starts to lose max LWT, heating capacity, and even more efficiency below that. (Losing efficiency a few days out of the year is a minor concern. Not being able to meet the heat loss and heat transfer for the building for a few days is a much more serious issue for health and comfort.) |
|