Hacker News new | ask | show | jobs
by josephcsible 1370 days ago
There's not a big risk of overcurrent here, since the 15A breaker will trip on overcurrent even when it's being backfed. The main hazard with these suicide cables is of electrocution, both inside your house due to the exposed blades being energized, and of linemen working to restore the power.
4 comments

The breaker isn't part of the circuit, though. Generator connects to in-wall distribution which connects to appliances. You only go across the circuit breaker on the way to the mains line, which is (hopefully) disconnected. Or else it's not, and indeed you'll get overcurrent protection for any attempt to power your neighbors appliances.
The breaker is the part of the circuit for the other circuits

you'd have something like

    gen -> circuit A -> main bus -> circuit b-> load
                           | 
                        main fuse/switch
                           |
                         outside
So loads on circuit A would not be protected by any fuse but ones at circuit B would.

Also circuit A would allow full generator amps to the devices there, no RCD protection either.

Most houses are wired with master breaker(s) connecting the house to mains lines, and various slave breakers connecting the various lines around the house to the master breaker(s).

If you plug a generator into a wall outlet, that power will pass through the slave breaker protecting that particular circuit as the power flows around to the rest of the house.

If you make a cable to plug a 15A outlet in your home into a 15A outlet on the generator, then hopefully the generator has its own breaker that would trip if too much current was drawn.

If you plug your house directly into a 40A outlet (which has a different shape) then, yeah, you're screwed.

If you plug your generator directly into a dryer/oven outlet, it should be on a dedicated branch circuit, and everything else you load in the house will actually have two breakers between it and the generator... one for the branch you're feeding from to the bus, and one from the bus to each branch circuit. And the generator probably has a third.

The only real difference between this setup and a proper generator hookup is a mechanical interlock so that the main and feeder branch breakers can't be on at the same time, and the gender of the generator hookup outlet.

This is generally why Solar installs don't work with the power out. They just shut off to prevent back feeding into the grid. (That and I think the dc->ac converter syncs with the 60hz of the US grid)

We don't have a battery but if you install a backup battery I believe there is circuity to cut the power off from the grid when powering your house.

Battery backups and generators definitely include an automatic cutoff switch (by law).
Isn’t the usual advice to turn off your main breaker? Both to protect a lineworker and to avoid stalling your generator by trying to power up the neighbourhood?
I’m not sure I want to see the Venn diagram of people who would buy this cable, and people who would know they need to do that.
Keep in mind that backfeeding your house won't actually work unless you disconnect from the grid. Your little generator cannot power the whole grid. You'll pop a breaker immediately. So even a total idiot isn't going to electrify the neighborhood (though they could cause serious momentary risk).

I know a couple people who use this approach. They're some of the most electrically savvy people I know. I don't get worked up about it.

They're out there.
Better advice is to use a proper inlet, with either a real transfer switch, or a mechanical lockout if allowed in your jurisdiction.

If you're using a cord like this, you almost certainly don't have anything but your brain preventing you from using it wrong. Brains aren't always enough.

if you do this you absolutely need to turn off your main breaker.
Do you think the people using this sort of cable acknowledge things like "the usual advice"?
I wonder what happens when the grid comes back up at a mismatched phase. If only mythbusters were still around. :-)
The fuse would blow, because you have mains ->main fuse -> circuit fuse -> generator
Maybe? What if it's a slow-blow fuse / breaker, and the phase is just a little bit off?
If it was alternator driven generator it would most likely drift into phase with the network, as the network would either break, or allow it to spin faster depending on in which direction the difference is.

That's actually how the big generators are synced, if there is less load you will see frequency of network increase slightly until the amount of generation drops, similarly in other way.

Inverter based one, hard to tell, entirely depending on code driving it.

But taking into consideration even 20V over low resistance wire could be 20+ amps it would probably trip pretty quickly.