by walrus01
1558 days ago
|
|
raised floors in general are a nightmare for grounding/bonding/differences in potential between racks, the steel floor structure, the building, and electrical conduits. there's a reason why almost nobody builds them new from a clean-sheet-of-paper design anymore for serious datacenter applications or ISP/telecom purposes, which are racks/cabinet on concrete slab and everything overhead now. it's much easier to ground/bond everything together using some very fat copper cables run along ladder rack overhead, and bond all the racks to that. |
|