The copper coming from "something" will be at least 1/2 inch thick, probably more so that it doesn't lose voltage. We're probably talking a 7/0 cable where 4/0 would be bare minimum.
1 comments

Probably larger than that. If they’re 200m from the transformer, 400A service requires (3) 1000kcmil cables per leg. 100m drops it to (3) 350kcmil which is still pretty beefy