Between neutral & earth? That's surely going to depend on the topology of your earthing system [0] - TN-C will be so low impedance you won't get much through your deliberate load at all, more with TN-C-S, but most luck with TN-S where neutral already has a long cable run full of impedance before it joins back up with earth, and you can add a small enough load that that path gets a non-negligible share of the current. [0] - https://en.wikipedia.org/wiki/Earthing_system#IEC_terminolog... |
|
Anything wireless is still out of the question unless real ground is there though. Without ground, a dedicated power harvesting circuit would certainly provide more power.
We experimented with harvesting, with 10cm antennas, it's just enough to do a single beep once 20-30 minutes using specialised ULP UHF radios, or RX for a few seconds once a minute.