That is a good way to test the generator without interruption, but at some point you still need to test the ATS under real world circumstances: unstable or suddenly missing utility power. Throwing the main covers one of those, and the other requires a little more planning and resources. |
|
You can test the system’s ability to detect loss of power or poor quality power by lifting sensing wires or injecting out of frequency or voltage range power with a test set, and load pickup and load testing we used a load bank. The actual hospital load is fed through bypass breakers during these tests so if the utility went out we would have to manually operate breakers to disconnect the load bank and swing the vital loads over to the generators.
If I am setting up electrical protection on a generator I don’t put a short circuit on the generator, I show the protection relay what it would see by injecting current and voltage with a relay test set and make sure the relay gives the signal to open the breaker when it should.
Greenfield hospital generation sites are straightforward to open the utility feeds since the vital loads are still fed through the old power system.