Wow, that's annoying, too bad that they wouldn't have a way to disconnect. IIRC, Princeton was able to operate some buildings off of the cogen plant during Hurricane Sandy, so I guess they had things engineered differently.
1 comments

All grid tie inverters shut off if power in the lines are down for safety reasons. You would need something special to switch over.
Yes of course, I just would have assumed the cost of that is pretty minor compared to the cost of the (apparently) 26 megawatt cogeneration plant
I don’t know — just imagine how many places the mains power is tied into all of the buildings. Each of those places would also need a mains cutoff, and they would need to all be thrown/active at the same time before the cogen plant could be activated independently. At a place the size of UC Berkeley, that would be a pretty big cost (and logistical nightmare).

If the system wasn’t designed for the switchover from the beginning, I can see how it would be considered impossible/not practical to do. Especially when this type of “blackout” was thought to be rare.

I’m sure the prior assumptions would be reconsidered today.

> just imagine how many places the mains power is tied into all of the buildings

Not many? As in, I don't think many buildings would have two separate power feeds. I'd expect a small number of very large connections from the cogen plant and the outside word into local distribution network(s), and then everything is single-path from there on.

But isn't that just because of legislation? As far as I can tell the system could just as easily throw a switch, test to make sure the switch was thrown, and then safely power locally. I know in California this is law, but I have never heard of a very good reason why it is technically difficult or inherently more dangerous to "air gap" your local power at the building rather than at the battery/power source.
Agreed. When I lived in Wisconsin the power would go out frequently during storms. Immediately I'd hear some neighbor's natural gas generators kick in and then a few minutes later I'd hear a few neighbors fire up their gasoline generators.

In both cases, they would flip over their home (or a sub panel) to the alternate power source (and disconnect it from the upstream grid). I looked into these systems and the natural gas ones could do this automatically using a kit available at Home Depot, and the gas generators required a manual switch, but were still very simple.

I looked into Solar in California and when I found out that most people can't use their systems during blackouts I asked about these generator systems that switch over and they basically said they had not seen equipment that could it and they didn't believe it was allowed anyway.

Solar is different from a generator, in that a generator is already producing AC, and as long as it produces a reasonable frequency and waveform you're good. Solar produces DC, which you then need to convert to AC, and the inverters that are typically installed are not able to do their own waveform shaping, depending on the grid to do it for them. It's possible to get inverters that handle this correctly, but they're more expensive, so typical home solar installs don't use them.
Or is it a horse and cart problem? Since there is legislation against it, there is not a demand, and prices have stayed high to sell them as "off grid" tech only? Most anybody would spend $500 extra on a 30k system for guaranteed power during blackouts.
There is no legislation against it where I am (Massachusetts), and there is still very limited demand for it because of the pricing.

> Most anybody would spend $500 extra on a 30k system for guaranteed power during blackouts.

To be clear, to get "guaranteed power during blackouts" out of solar, you need both a more expensive inverter ($1k or so last I checked) and batteries ($5-15k last I checked). If you're OK power only when it's sunny _and_ a blackoutm you might be able to do just the more expensive inverter, maybe. I'm not actually sure whether that work without a battery sink for your unused current.

Inverters are only used for DC to AC conversion, cogeneration sets are conventional prime mover setups that output 3-phase AC directly. The problem likely has to do with islanded grid stability, without the grid you have to take care of power factor correction and grid voltage regulation yourself, this can get pretty dicey if you don't have direct control or knowledge of the type of loads you'll have.
In an islanded mode of operation you also need to match load and generation to maintain system frequency, which is tough to do with cogen and non-controlled loads.

Basically, it can work, but the whole system is going to need to be engineered for it from the outset.